:::Technical Index:::

1. Bleeder Rate: 40%-95% (Higher resistance rate of soil, more effective in resistance reducing)
2. Stability and long effects, validity period will be 20~30 years in theory
3. Increased greatly in water protection and observation

Report

4. Other indexes please see detail as bellow:

Index
Item
Requirement
Value
Result
1
Resistance Measurement in Indoor Temperature
p≤5
p=0.50 .m△
Accord 6
2
a. Water Lose
After Test:
p=0.60 .m
Pass
b. Cool & Hot Cycle Test
p≤5.m
p=0.48 .m
Pass
c. Marinate Test
 
a  a
p=0.60 .m
Pass
3
Impact Current Durability Test
△R%≤20%
△R%=2.4%
Pass
4
Power Current Durability Test
△R%≤20%
△R%=-27%
Pass
5
PH Value Measurement   

 Cautery Test of Bleeder Agent for Steel Earth

PH value between 7-12

 Surface Cautery Rate in Average≤0.03mm/year

PH=8

Surface Cautery Range in Average (mm/year)

Accord
6
Cautery Test of Bleeder Agent for Steel Earth  
 
a

Round Steel: 0.21    0.02-0.025    Flat Steel: 0.026   0.021-0.028   Galvanized Round Steel:0.029   0.024-0.030  Galvanized Flat Steel: 0.030   0.018-0.030

Accord